1. Support parallel system, which can be expanded to MW level                                                                                 
2. Support multiple battery input, improve battery cycle life
3. Built-in fire protection system
4. Built-in EMS function, improve energy efficiency
Application: Photovoltaic Power Station Energy Storage, High-End Villa, Communication Base Station, Communication Room
            
        


Model  | HXHV-15000W | HXHV-20000W | HXHV-25000W | HXHV-30000W | 
Norminal Voltage  | 153.6V(48S) | 204.8V(64S) | 256V(80S) | 307.2V(96S) | 
Norminal Capacity  | 100Ah | 100Ah | 100Ah | 100Ah | 
Energy  | 15.36KWh | 20.48KWh | 25.6KWh | 30.72KWh | 
Internal Impedance  | ≤80mΩ | ≤100mΩ | ≤120mΩ | ≤150mΩ | 
Cycle Life  | ≥5000 cycles @80%DOD,25℃,0.5C ≥4000 cycles @80%DOD,40℃,0.5C  | |||
Design Life  | ≥10 years | |||
Charge Voltage  | 168V±0.5V | 228V±0.5V | 284V±0.5V | 340V±0.5V | 
Max Operating Current  | 100A | |||
Cut-off Voltage  | 135V±0.5V | 180V±0.5V | 225V±0.5V | 270V±0.5V | 
Charge Temperature  | 0℃~60℃ | |||
Discharge Temperature  | -20℃~60℃ | |||
Storage Environment  | -40℃~55℃@60%±25% humidity | |||
Dimension(mm)  | 745*415*590 | 930*415*590 | 1120*415*590 | 1300*415*590 | 
Weight(kg)  | 195kg | 260kg | 310kg | 360kg | 
Communication Protocol  | RS232-PC, RS485(B)-PC, RS485(A)-Inverter, Canbus-Inverter | |||
Certification  | UN38.3,MSDS,UL1973,IEC62619 | |||